消防管道安装离墙间距 Fire service pipe installation spacing from the wall


发布时间:

2024-10-16

‌‌高位消防水箱外壁与建筑本体结构墙面或其他池壁之间的净距‌应满足施工或装配的需要。 The clear distance between the outer wall of the high level fire water tank and the structural wall of the building body or other pool wall should meet the needs of construction or assembly.

‌‌高位消防水箱外壁与建筑本体结构墙面或其他池壁之间的净距‌应满足施工或装配的需要。无管道的侧面,净距不宜小于0.7m;安装有管道的侧面,净距不宜小于1.0m,且管道外壁与建筑本体墙面之间的通道宽度不宜小于0.6m。设有人孔的水箱顶,其顶面与其上面的建筑物本体板底的净空不应小于0.8m。

‌‌水泵接合器的安装要求‌应设在室外便于消防车使用的地点,且距室外消火栓或消防水池的距离不宜小于15m,并不宜大于40m。墙壁消防水泵接合器的安装高度距地面宜为0.70m;与墙面上的门、‌窗、孔、‌洞的净距离不应小于2.0m,且不应安装在玻璃幕墙下方。地下消防水泵接合器的安装,应使进水口与井盖底面的距离不大于0.40m,且不应小于井盖的半径。

‌市政消火栓的安装要求‌距路边不宜小于0.5m,并不应大于2.0m。市政消火栓距建筑外墙或外墙边缘不宜小于5.0m。

‌室内消火栓的安装要求‌栓口离地面的高度为1.1m,出水方向应便于消防水带的敷设,并宜与设置消火栓的墙面成90°角或向下。

‌其他相关规范和注意事项‌包括管道安装位置应符合设计要求,管道的中心线与梁、柱、楼板的最小距离应符合相关规定。此外,‌橡胶密封圈应无破损和变形,‌沟槽式管件的安装应符合规范要求等。

The clear distance between the outer wall of the high level fire water tank and the structural wall of the building body or other pool wall should meet the needs of construction or assembly. No pipeline side, the clearance should not be less than 0.7m; installation of pipeline side, the clearance should not be less than 1.0m, and the pipeline wall and the building wall between the channel width should not be less than 0.6m. with a manhole tank top, the top surface of the building above the bottom of the slab clearance should not be less than 0.8m.

The installation requirements of the water pump connector should be located in the outdoor location convenient for the use of fire engines, and the distance from the outdoor fire hydrant or fire pool should not be less than 15m, and should not be greater than 40m. the installation height of the wall fire pump connector from the ground should be 0.70m; and the door on the wall, Windows, holes, holes in the wall of the net distance should not be less than 2.0m, and should not be installed under the glass curtain wall. The installation of underground fire pump connector should make the distance between the water inlet and the bottom surface of the well cover is not more than 0.40m, and should not be less than the radius of the well cover.

Municipal fire hydrant installation requirements from the curb should not be less than 0.5m, and should not be greater than 2.0 m. Municipal fire hydrant from the building facade or the edge of the facade should not be less than 5.0m.

The installation of indoor fire hydrants requires that the height of the spigot from the ground is 1.1m, and the direction of the water outlet should be convenient for the laying of fire hoses, and it is appropriate to set up a fire hydrant with the wall into a 90 ° angle or down.

Other relevant norms and considerations include the pipe installation location should meet the design requirements, the centerline of the pipe and the minimum distance between the beams, columns, floor slabs should comply with the relevant provisions. In addition, the rubber sealing ring should be free of breakage and deformation, and the installation of grooved pipe fittings should be in accordance with the specification requirements.